Battery Charger FDPAB 40-200A/3U-M
Details: Battery Charger FDPAB 40-200A/3U-M
Newer technologies of the rectifier based on the high frequency voltage conversion adapter that enables you to create the technical parameters far beyond the conventional rectifier and to the quality of output characteristics, the size and weight, and the benefits in terms of loss of electricity output.
The advantages of this technology, especially comes to the fore in demanding consumers, especially when the rectifiers are used as rechargeable battery chargers where the harsh demands placed on the rectifier control output parameters, as in the process of charging to avoid damage to the batteries. With new high-adapter-charger can be controlled to maintain the charging parameters (voltage and current) within the set limits with a tolerance ± 1%. Output ripple voltage is less than 0.5% of the maximum output voltage.
Limits of current and the charging voltage can be adjusted depending on battery used and according to:
- Battery type: VRLA lead, lead-gel, ordinary lead, nickel cadmium
- the number of series-connected articles
- the capacity of the battery
- Battery temperature
Charging regimes to be elected as follows:
- IU charging characteristic
- IUI charging characteristics
- Wa characteristics of constant power
- PWA characteristics of pulse charging current
When the rectifier are controlled microprocessor unit charging parameters are stored in the memory adapter (SD card) and can be monitored on a permanent connection through the "Ethernet" on your computer or cell switch from SD cards over the RS232 port on the laptop. Using the RS232 port are set (change) the parameters of charge.
TECHNICAL DATA:
Input voltage: 3x400V AC, +10%, -15%, 47-53Hz
Maximum input current: <18A
The shape of input current: ≥ 0.85
Input protected by automatic circuit breakers: 2x (3x16)
RSO degree of protection: B according to EN55022
The choice of parameters according to charging the connected battery-using the buttons S1, S2 and S3:
Ordinal number / type of batteries / voltage / current
0 = SBM260-NiCd (24V, 55A)
1 = SBM369-NiCd (24V, 75A)
2 = SBM135-NiCd (30V, 30A)
3 = SBM281-NiCd (30V, 55A)
4 = SBM334-NiCd (30V, 70A)
5 = SBM340-NiCd (33V, 70A)
6 = SBM375-NiCd (33V, 75A)
7 = SBM450-NiCd (33V, 90A)
Operating characteristics of filling: IU
Output protected against short circuit: Electronic limit by default charging parameters, Automatic circuit 2x120
Output protected from wrong polarity battery, battery charger FDPAB 40-200A/3U-M not start charging until the battery is connected to the correct polarity and voltage ≥ 8V
Blockade output contactor:
-A case of wrong polarity
Case-2A Iout ≤ 1 sec in time.
UB-case <8V
The accuracy of maintaining the set parametatara: ± 1% of the default
Output voltage ripple: ≤ ± 0.5% of the default voltage VEF
Efficiency: ≥ 0.9 at the maximum output power
Protection:
Input:
- Overvoltage protection level IV derived varistors 230, leakage current of 20kA impulse
- Automatic input circuit: 3x16Ax2
Output:
- Battery fuse 2x120
- An electronic limit
Other protection:
Thermal protection against overheating of components involvement fan and lock work
Measuring the local numerical instruments:
Current charging
Voltage charging
Signaling a local light-emitting diodes:
-The presence of mains voltage (L1, L2, L3), lamps (red)
Input-voltage converter FDSIN 50-40A (P1, P2), LED (red)
Charge-mode, LED (yellow)
-Supplementation regimen (maintenance), IB <3A, LED (green)
Fault-charger, LED (red)
Showing locally on LCD screen:
Elected-type battery or the number of articles / capacity / voltage / current
Charge-duration
The standards for battery: DIN 41 733, IEC 60950
Connections:
Input:
Cable length 10m 5x4 mm2 with the industry's 5-pole plug
Output:
Appliance-connectors for the supply of 300A
Communication:
- RS 232 - PC
- UTP RJ 45 - Ethernet
Operating temperature range: -20 ° C to +40 ° C
Dimensions (VxDxŠ): 1600x400x600 mm
Weight: 90 kg
Category